Environmental Conditions; General Installation Instructions - Techem 70130227 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 98

Environmental conditions

• Operating conditions / measurement range:
Temperature measurement range:
Medium temperature range (cold meter):
• Ambient temperature:
• Radio (if activated):
Transmission frequency: 868.95MHz
Transmission rating:< 25mW
• Output measurement: Cycle 32 sec.
• Installation: enclosed spaces
• Do not disconnect the volume measuring section and temperature sensors from the
computer unit.
Installation

General installation instructions

• Observe the environmental conditions!
• Select installation locations where the permissible temperature spreads are not
undercut.
• The volume measuring section is best installed in the outlet, that is to say on the warm
side of the refrigeration cycle.
• All components must be insulated impermeably after installation.
(as applicable using insulation set art. no.: 330300)
• Install ideally in the area of the variable flow.
• The meter must be protected against magnetite and dirt for the device's entire working life.
• Shut-off valves must be installed in front of the strainer and behind the meter.
!
When selecting the installation location, pay attention to the length of the fixed
connected sensor cable.
• Do not carry out any welding, soldering or drilling work in the vicinity of the meter.
• Only install meters in operational systems.
• Protect meters against damages from impacts or vibration.
When commissioning, open the shut-off valves slowly.
Q 0 °C...50 °C
Q 5 °C...50 °C
Q 5 °C...55 °C
DQ 3 K...50 K
11
GB

Publicidad

Tabla de contenido
loading

Tabla de contenido