Switching To Normal Mode From Manual Bypass Mode (Parallel Ups-Mus) - Tripp-Lite SU120KX2 Manual Del Propietário

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8 – Start-Up, Shutdown and Bypass
1
8-11 Switching to Normal Mode from Manual Bypass Mode (Parallel UPS—MUS)
If the UPS systems have external battery cabinets connected,
1
2
switch on the external battery cabinet circuit breaker switch of
each battery cabinet for each UPS.
3
4
Switch on the bypass input circuit breaker switch
2
output circuit breaker switch
5
6
Confirm that all UPS systems are in manual bypass mode, then
3
switch off the manual bypass input circuit breaker switch
of each UPS system. The LCD screen will read "ON AUTO
BYPASS".
7
8
Switch on the main input circuit breaker switch
4
system.
9
10
Press the ON button
5
A
you hear a beep), then release the button. Press the ON button
for each of the remaining UPS system for 3 seconds (until you
hear a beep), then release the button. When the inverters of all
UPS systems are operating normally, they will switch to on-line
11
(normal) mode at the same time.
12
13
14
12-212-93-3141.indb 28
and the
Q2
Q4
of each UPS system.
Q3
of each UPS
Q1
of the first UPS system for 3 seconds (until
(continued)
1
Q4
Output
Manual
Bypass
2
Q3
Output
Manual
Bypass
3
Output
Manual
Bypass
4
5
28
Q2
Bypass
Main
Input
Input
Bypass
Main
Input
Input
Q1
Bypass
Main
Input
Input
A
12/28/2012 11:17:51 AM

Publicidad

Tabla de contenido
loading

Tabla de contenido