Block "Boiler"
91
92
93
94
95
96
97
98
Block "Pump M1"
99
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
86 P-band of control
(Xp)
(1.0...100.0)
87 Integral action time
of control (Tn)
(10...873)
Boiler operating
mode
Maximum limitation
of boiler temperature
(25...140)
Minimum limitation
of boiler temperature
Switching differential
of boiler
Minimum limitation
of burner running
time
Release limit for
50 °C×min
second burner stage
Reset limit for sec-
10 °C×min
ond burner stage
Waiting time for
second burner stage
Operating mode
pump M1
74 319 0619 0 a
32.0 °C
°C
...................
120 s
s
......................
0 = with manual shutdown
0
(0...2)
.........................
1 = with automatic shutdown
2 = without shutdown
95 °C
No safety function
°C
...................
10 °C
(5...140)
°C
...................
6 °C
(1...20)
°C
...................
4 min
(0...10)
min
................
°C×min
(0...500)
..........
°C×min
(0...500)
..........
20 min
(0...40)
min
................
0 = circulating pump without
1
(0...3)
.........................
1 = circulating pump with shut-
17.04.2008
(
key)
(OFF when there is no
demand for heat)
shutdown in the case of pro-
tective boiler startup
down in the case of protec-
tive boiler startup
51/288
en