Apparent power (@ 230V single phase systems 1Ph, cos=0, f=50/60Hz)
FS clamp
10A
10A FS 200
200A FS 1000
1000A FS 3000
Power factor (@ 230V single phase systems 1Ph, f=50/60Hz, current ≥10%FS)
Range
0.70c 1.00 0.70i
cos (@ 230V single phase systems 1Ph, f=50/60Hz, current ≥10%FS)
Range
0.70c 1.00 0.70i
Voltage harmonics (@ 230V single phase systems 1Ph, f=50/60Hz)
Range [%]
0.1 100.0
Fundamental frequency: 50/60Hz ±5%
Harmonics are zeroed in the followed conditions:
DC : if the DC value <0.5% fundamental value or if the DC value < 1.0V
1° harmonic: if the value of 1°harmonic < 15V (not displayed)
2nd 25th harmonics: if harmonic value <0.5% fundamental value or if the value < 1.0V
Current harmonics (f=50/60Hz)
Range [%]
0.1 100.0
Harmonics are zeroed in the followed conditions:
DC : if the DC value <0.5% fundamental value or if the DC value < 5mV
1° harmonic: if the value of 1°harmonic <5mV (not displayed)
2nd 25th harmonics: if harmonic value <0.5% fundamental value or if the value <5mV
Range [kVA]
Resolution [kVA]
0.000 9.999
0.00 999.99
0.0 999.9
0 9999
Resolution
0.01
Resolution
0.01
Resolution [%]
0.1
Resolution [%]
0.1
EN - 10
EASYTEST-COMBI519-COMBI521
0.001
0.01
0.1
1
Accuracy
(2.0rdg + 3dgt)
Accuracy
(2.0rdg + 3dgt)
Order
00, 02 25
Order
00, 02 25
Quick reference guide
Accuracy
(2.0rdg + 5 dgt)
Accuracy
(5.0rdg + 5dgt)
Accuracy