• Check that the maximum pressure has not changed.
• Put the protective cap "D" back on.
• To end TEST mode, select another mode.
Key
B
Pressure point
C
Modureg cable
D
Protective cap
E
Minimum pressure adjustment
G
Maximum pressure adjustment
After checking or adjusting the pressure,
it is mandatory to seal the adjustment
screw with paint or a specific seal.
Max. heating power adjustment
Refer to the Installer parameters menu section
Lighting power adjustment
Refer to the Installer parameters menu section
Installer Parameters menu
The card has 11 transparent parameters that can be modified either by Remote Control (Service parameters
menu) or by itself (Installer Parameters Menu except for the last three: 9,10 and 11):
Num.
Parameters menu
1
Max. heating power
2
Gas type selection
3
Lighting Power
4
Heating idle time
5
Heating pump Post-Circulation
6
Heating user max. setpoint
7
Hot water user max. setpoint
8
Heating sensor selection
9
Heating ramp
10
Mains Voltage Frequency
11
Switching off burner in hot water mode
Remote Timer Control modification occurs by entering its Service parameters menu (refer to the relevant manual):
the order and range correspond exactly to that given in the table.
Modification from card occurs as follows.
The parameters, named in the previous table P1÷P8, can be displayed and possibly modified from the Installer Pa-
rameters menu by decoding of the LEDs and position, for different time intervals, of the selector. The method for
accessing, displaying and/or modifying a number of parameters and exiting the menu is described by means of the
following flow chart.
26
All manuals and user guides at all-guides.com
Range
0-100%
0=Natural gas,1=LPG
0-60%
0=0minutes, 1=2.5 minutes
0=0minutes, 1=2.5 minutes
30°C, 40°C, 85°C
0=55°C, 1=65°C
0=Double sensor,
1=Safety Therm. + Sensor
1-20°C/min
0=50Hz,1=60Hz
0=Fixed, 1=Tied to setp.
2=For solar heat. sys.1, 3= For
solar heat. sys.2
Cod. 3540F130 - 03/2007 (Rev. 00)
TAURA 32 MC
Fig. 3
Default
100%
0=Natural gas
50%
1=2.5 minutes
1=2.5 minutes
85°C
0=55°C
1=Double sensor
10°C/min
0=50Hz
1=setp.