6. Specifications
MODEL
CAPACITY*
INPUT
Nominal Voltage
Low Line Loss
Low Line Comeback
Voltage
Range
High Line Loss
High Line
Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output Voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC Mode
Overload
Battery Mode
Current Crest Ratio
Harmonic Distortion
Line→ Battery
Transfer
Time
Inverter→Bypass 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
EFFICIENCY
AC Mode
Battery Mode
ECO Mode
20 Kw
20 Kva / 20 Kw
208/220 VAC (Ph-Ph) 3 x 120/127
138 VAC(Ph- Ph ) ± 3 % at 50% Load
172 VAC(Ph- Ph) ± 3 % at 100% Load
270 VAC(Ph- Ph) ± 3 % at 50% Load
253 VAC(Ph- Ph) ± 3 % at 100% Load
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 1 hour; 110%~130%: 1min; >130% : 1sec
100%~110%: 30sec; 110%~130%: 10sec; >130% : 1sec
≦ 1 % @ 100% Linear Load; ≦ 3 % @ 100% Non-linear Load (PF≥0.8)
47
20Kw
20KVA / 20KW 30KVA/30KW 40KVA/40KW
VAC (Ph-N)
Low Line Loss Voltage + 5V
High Line Loss Voltage - 5V
44Hz ~ 55 Hz @ 50Hz system
54Hz ~ 66 Hz @ 60Hz system
3 Phase with Neutral
≧ 0.99 at 100% Load
3 Phase with Neutral
3 x 208/220 VAC (Ph-Ph)
3 x 120/127 VAC (Ph-N)
± 1%
44Hz ~ 55 Hz @ 50Hz system
54Hz ~ 66 Hz @ 60Hz system
3:1 max
0 ms
96%
94.5%
99%
30Kw
40Kw