MODEL
BATTERY
Type
Numbers
Standard
Recharge Time
Model
Charging Current
(max.)
Charging Voltage
Type
Numbers
Long-run
Charging Current
Model
(max.)
Charging Voltage
PHYSICAL
Dimension,
Standard
D x W x H (mm)
Model
Net Weight (kgs)
Dimension,
Long-run
D x W x H (mm)
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
**Product specifications are subject to change without further notice.
2~4 hours recover to 90% capacity
1A/2A/3A/4A (Adjustable)
4A/8A/12A (Adjustable)
Optional parallel up to Max.
+/- 13.65 VDC * N ± 1% (N = 8~10)
865 x 300 x 1020
181
865 x 300 x 1020
80
0 ~ 40°C (the battery life will down when > 25°C)
Up to 3000 m / 10000 ft without derating
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP manager and web browser
48
20Kw
12 V / 9 Ah
(10+10)pcs
x 3 strings
+/-136.5 VDC ± 1%
Depending on applications
8 ~ 10 (adjustable)
20A
231
81
<0~95% and non-condensing
Less than 56dB @ 1 Meter
30Kw
40Kw
NA
4A/8A/12A/16A (Adjustable)
Optional parallel up to Max. 24A
NA
790 x 420 x 1200
150
160