Tech data
Permissible ambient
temperature
Protection index
Protection class
Identification number
Ball pressure test
temperature
Degree of pollution
Table 2
Tech data
°C
°C
20
14772
44
26
11500
50
32
9043
56
38
7147
62
Table 3
Measurements for cylinder temperature sensor
(TS2...)
°C 
°C
– 30 364900 25 20000 80
– 20 198400 30 16090 90
– 10 112400 35 12800 95
0
66050
40 10610 100 1344
5
50000
50 7166
10
40030
60 4943
15
32000
70 3478
20
25030
75 2900
Table 4
Collector temperature sensor measurements (TS1)
2.9

Additional accessories

For detailed information about suitable accessories, refer to
the catalogue or Internet page of the manufacturer.
For solar thermal system 1:
– Solar pump; connection to PS1
– electronically regulated pump (pulse width modulation
or 0-10 V); connection to PS1 and OS1
– Temperature sensor; connection to TS1
– Temperature sensor at the bottom of the first cylinder;
connection to TS2
Additionally for cylinder 1 external heat exchanger (E):
– Heat exchanger pump; connection to VS1, PS2, PS3
– Temperature sensor on heat exchanger; connection to
TS3
30
0 ... 60 °C
IP 44
I
Data plate ( Fig. 18 at the
end of document)
75 °C
2
°C
57301
68
2488
4608
74
2053
3723
80
1704
3932
86
1421
°C
°C
2492
150 364
1816
160 290
1500
170 233
180 189
110 1009
190 155
120 768
200 127
130 592
140 461
Additionally for transfer system (I):
– Cylinder transfer pump; connection to VS1, PS2, PS3
For thermal disinfection (K):
– Thermal disinfection pump; connection to VS1, PS2,
PS3
Additionally for heat meter (L):
– Temperature sensor in flow to solar collector;
connection to TS3
– Temperature sensor in return from solar collector;
connection to IS1
– Water meter; connection to IS1
For freshwater system:
Additionally for circulation (A):
– DHW circulation pump; connection to PS1
Additionally for temperature-dependent return feed (B):
– Valve for return feed; connection to VS1
– Cylinder temperature sensor for changeover
temperature; connection to TS3
Additionally for preheating system (C, D):
– Cylinder primary pump; connection to PS1
Additionally for freshwater cascade (E):
– Cascade valves 2 – 4; connection to PS1
Installation of additional accessories
▶ Install the additional accessories in accordance with legal
regulations and the instructions supplied.

2.10 Cleaning

▶ Wipe the enclosure with a damp cloth if necessary. Never
use aggressive or caustic cleaning agents for this.