4.3.10 Final X to Y check: compare X to Y axes to be sure that your adjusted

4.3.11 Press the key on the remote with the small dot to save the calibration
wc_tx000806gb.fm
All manuals and user guides at all-guides.com
4.3.8.3
With detector, mark center of the beam (+Y).
4.3.8.4
At 100 ft., the marks should be no more than 1/4" apart. (At
30 m, no more than 6 mm apart.) If the marks are close
enough, Y axis is within calibration; proceed to Step 4.3.10.
If the marks are not close enough, the laser must be calibrated to bring
the beam to the center of the two Y marks. Use the (^) or (v) ARROW
keys on the remote or laser keypad to move beam up or down to the
center.
calibration is within specification of ± 1/8"at 100 ft. (± 3 mm at 30 m).
Turn the laser 90° each time; the marks for +X, -Y, -X, +Y should not
be more than 1/4" (6 mm) apart.
(or press the MAN/AUTO key on the laser).
If you are not sure of the calibration and do not wish to save it, do not
press the small dot, and turn the laser off with the On/Off key.
EN-21