Specifications
Arc Fault Test: (12) 112 A pulses
Pulse Width: 400 µs
Repetition Rate: 120 Hz
Ground Fault Test: 7 mA at 120 VAC
Polarity Indicator: 3 LEDs indicate proper wiring to the outlet being tested
Power: 120 VAC, 15 A or 20 A branch circuit
Operating Temperature: -25 °C to 80 °C (-13 °F to 176 °F)
Storage Temperature: -55 °C to 80 °C (-67 °F to 176 °F)
Maintenance
• Do not attempt to repair this unit. It contains no user-serviceable
parts.
• Do not expose the unit to extremes in temperature or high humidity.
Refer to "Specifications."
Failure to observe these precautions can result in injury and can damage
the unit.
Cleaning
Periodically wipe the case with a damp cloth and mild detergent; do not use
abrasives or solvents.