Installing Heat Reclaim Ventilation
Installation Procedures
Do not install the unit in:
•
Places close to high temperature locations or naked fires; otherwise, fire accident or overheating may occur.
•
Places where oil mist or gasoline exists, such as kitchen; otherwise, fire may occur.
•
Places where poisonous gases or corrosive material (acid and alkali solvents) are to be found, such as machine
shop and chemical plant. Places where leakage of inflammable gases is possible shall also be avoided.
•
Places with high humidity, such as bathroom, where electric shock or creepage and other troubles may take
place.
•
Places close to machines sending out electromagnetic waves, which may interrupt the operation of control system
and cause failure.
CAUTION:
Please make sure that temperature and humidity in places where air inlet and outlet grille is installed are
controlled within prescribed range under operating conditions. Do not install the grille in refrigerator vehicle,
low temperature places or warm water swimming pool; otherwise, short circuit or fire may ensue. Vehicles or
vessels shall also be avoided.
Preparation Prior to Installation
Accessories and fittings necessary for installation shall be kept and must not be discarded.
1. Transporting the Unit
•
Decide on transporting route and do not unpack before arriving at installation site.
•
When unpacking is compulsory, please use soft rope or adopt the "rope plus angle of protection" approach to
lifting devices so that scuffing or damages can be avoided.
•
When moving unpacked units, lift the unit by hoist hook, and not by any other objects on the unit (air hose joints in
particular).
CAUTION:
Concerned specialists shall teach users how to correctly operate the unit with aid from the manual (especially air
screen service and operation procedures).
2. Accessories: Other parts not shown below shall be prepared by users.
Designation
Number
Appearance
Air Hose Joint Flange
4
M4 Tapping screw
16
15
Lace
Manual
2
1