Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit
GMV-ND40~63PL/B-T
GMV-ND72PL/B-T
4.4.3 Installation of Air-return Duct
1
Square flange is defaulted to be fitted on the back before ex-factory. Air-return cover is on the
bottom, as shown in Fig.4.4.4.
2
If air return from the bottom is needed, switch the positions of square flange and air-return cover.
3
Use a clincher to connect air-return duct to the air-return opening of indoor unit. The other end of
air-return duct connects with the air-return louver. In order to adjust the height conveniently, you
can make a folded canvas duct and have it strengthened by 8# iron wire.
4
Air return from the bottom will produce more noise than air return from the back. So we suggest you
to add a noise damper and static pressure case to lower noise if you choose air return from the
bottom.
5
Select the appropriate installation way based on actual construction and maintenance needs, as
shown in Fig.4.4.5.
No.
1
2
3
4.4.4 Installation of Fresh Air Duct
1
If a fresh air duct is needed, remove the fresh air baffle as shown in Fig.4.4.6. If a fresh air duct is
not needed, block the gap on the baffle with sponge.
2
Install circular flange so that fresh air duct can be easily connected, as shown in Fig.4.4.7.
3
Both air duct and circular flange need to be well-sealed and insulated.
4
Fresh air should be the air that has been filtered.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
122
122
Name
Return Air Inlet (with filter)
Canvas Duct
Return Air Duct
885
1185
Fig 4.4.4
Fig 4.4.5
No.
4
5
6
14
200
1000
200
1300
Name
Indoor unit
Supply Air Duct
Grille