3. Battery Cabinet Installation
3.4 Package Contents
Part Number
933BF6
Owner's Manual
73184C
Battery Cable
731891
Battery Cable
731856
Battery Shorts/
Jumper Cables
820606
Cushion
Various P/N
Battery Cables
for "-NIB"
Models
Copper Jumper
1038F2
Bars
3.5 Internal Wiring (Typical)
• Battery cabinets use multiple 12V DC batteries connected in series to provide nominal DC voltage of 240V DC (±120V DC).
• Internal cabling is sized for specific application load currents. Do not use any other cable size other than the one provided in
the battery cabinet.
• Each battery cabinet shelf includes a specific wiring diagram. Refer to section 5. Installation for battery installation details.
• All circuit breakers are in the middle tier of the battery cabinet.
• All load connection polarities will be labeled as "+" (battery positive), "-" (battery negative) and "N" (battery center tap) for
±120V DC strings.
• All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load or
UPS.
BP240V09
Description
BP240V09K
Yes
Length 1.3 m Cables
2
with Anderson
connector terminals
Length 3 m Cables
n/a
with Anderson
connector terminals
Copper bars for
n/a
interconnecting
adjacent batteries
Battery cabinet
n/a
bracket/panel
assembly
For connecting the
n/a
battery strings to the
cabinet
Copper bars for
n/a
interconnecting
adjacent batteries
BP240V09-
NIB
BP240V40
Yes
Yes
2
n/a
n/a
2
72
n/a
16
n/a
n/a
n/a
n/a
n/a
8
BP240V40-
BP240V40L-
BP240V40L
NIB
Yes
Yes
n/a
n/a
2
2
n/a
n/a
n/a
n/a
n/a
9
n/a
14
NIB
Yes
n/a
2
n/a
n/a
16
28