6. Operation and Configuration of S3M UPS Models
and Battery Cabinets
6.3.3 Battery Setup
Click BATT Setup
Float Temp. Compen.: The temperature sensor compensation setting maybe changed to Enable when a battery temperature
sensor is connected to the UPS system's RJ45 rear port.
Temp Sensor Select: Set the temperature sensor type to NTC for single and short distances. Set the temperature sensor type
to RS485 for multiple and far distances.