The gaskets at the inlet connections (if provided) must be replaced when re-assembling!
Make sure that the gaskets sit properly in the mounting and that the screws are tightened.
If the pressure regulator is installed in the flow direction downstream from
another pressure regulator, the supply pressure range must correspond to the regulated
pressure range of the first pressure regulator, with consideration of the pressure loss in the
piping between the two devices.

LEAK CHECK

The liquefied gas unit must be checked for leaks by an expert* before the first start-up, during
checking and maintenance work, before the re-start and after important changes and repair
work. See USER QUALIFICATION!
Test connection for leak tester
A leak tester can be connected to the test connection for pressure and leak testing of the LPG
system.
6. Unscrew the test hose and screw the screw cap back onto the test connection.
7. Spray the connection with a foam producing substance according to EN 14291
(e.g. leak detector spray, order no. 02 601 00).
8. Check the leak-tightness at the connection by seeing whether bubbles form
in the foam producing substance.
9. Screw the screw cap back onto the test connection.
Observe the applicable national installation regulations for LPG systems.
*Experts are particularly those who, on the basis of their training, knowledge and experience
gained during practical activity, guarantee that they carry out the inspection properly.

OPERATION

Use this product only when you have carefully read the assembly and operating
manual.
For your own safety, observe all the safety messages in this assembly and
operating manual.
Please also consider the safety of others.
16 / 74
1. Close all shut-off fittings on the connected
2. Close the tank valve.
3. Unscrew the screw cap of the test connection.
4. Screw the test hose (order no. 02 618 06) on
5. Carry out leak testing with the test pump at
Observe EN 1949.
consuming devices .
the test connection.
max. 150 mbar.
Caramatic DriveOne
Artikel-Nr. 71 813 50 a