Fault Diagnostics - Lockouts; Fuel Pre-Heating Function (Only For Suitable Applications); Shut-Down Test; Intermittent Operation - Riello MO550-BWG Instrucciones De Instalación, Uso Y Mantenimiento

Caja de control
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.7.2

Fault diagnostics - lockouts

Fault description
Extraneous light (false flame signal)
Electrical power voltage fault
Electrical power frequency fault
Flame control voltage fault
Reset button / Remote reset anomaly
Lockout for no flame after Ts
Lockout for extraneous light signal or for parasite flame
Lockout for maximum number of cycle repetitions (flame
loss during operation)
Lockout for fan motor error
Lockout for fault with the circuit within the 1st stage valve
control
Lockout for fault with the circuit within the 2nd stage valve
control
Lockout for pre-heating not finished
Lockout for eeprom error
Short-circuit 1st stage valve lockout
Key
ON
3.7.3
Fuel pre-heating function (only for suitable
applications)
The burner is equipped with the fuel pre-heating function, in the
presence of a start request from the heat request thermostat of
the boiler, the burner awaits the closure of the start-up thermostat
(or pre-heating, K) positioned on the nozzle holder.
If the start-up thermostat (or the pre-heating one) does not close
within 600 seconds, the burner goes into lockout mode.
If the flame goes out during operation, the burner carries out re-
cycling if the contact of the start up thermostat (or the pre-heating
one, K) is closed.
If the flame goes out during operation and the contact of the start
up thermostat (or the pre-heating one, K) is open, the purging
stops and the burner waiting for the closure of the contact of the
start up thermostat (or the pre-heating one, K) to restart with the
pre-purging time.
3.7.4

Shut-down test

If the reset push-button is pressed during running operations for
more than 5 seconds and less of 10 seconds the burner will per-
form a shutdown, the oil valve is closed, the flame stop and start-
up sequence restarts.
If the switch off test is enabled, the number of repetitions of the
start up sequence (see paragraph "Recycle and limit of repeti-
tions" on page 11) and the number of possible resets (see par-
agraph "Protection reset" on page 11), are reset.
20138365
Electrical data and operating times
OFF
Colour code
RED
ORANGE
GREEN
Reset button colour
GREEN, RED
blinking alternately
ORANGE
slow blinking
ORANGE
ORANGE, GREEN
fast blinking alternately
GREEN, RED
fast blinking alternately
RED
RED
blink
RED
Fast blinking
RED, ORANGE
blinking inverted
RED, GREEN
blinking inverted
RED
blinking inverted
RED blinking
ORANGE, GREEN
blinking alternately
RED, GREEN
slow blinking
3.7.5

Intermittent operation

After 24 hours of continuous operation, the control box starts the
automatic switch-off sequence, followed by a restart, in order to
check for a possible fault with the flame sensor. This automatic
switch-off can be fixed at 1 hour, (see paragraph "The deactiva-
tion of the automatic pre-heating is not lost if the switching
off test is activated or if the heat request thermostat opens."
Tab. E
on page 14).
The modification of the parameter setting for intermittent opera-
tion takes effect if:
 during the heat request, the switching off test function is ena-
bled;
 there is a flame loss;
 the heat request switches off and then later restarts;
 the control box switches off and restarts;
 the automatic restarting of the intermittent function occurs
(1hour/24hours).
10
GB
Seconds
Colour code
0.5
0.5
2.5
2.5
-
-
0.2
0.2
0.2
0.2
-
-
0.5
0.5
0.2
0.2
2.5
0.5
2.5
0.5
2.5
0.5
0.5
2.5
0.5
0.5
2.5
2.5
Tab. D

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

20136740

Tabla de contenido