Mounting
1
3b
See Figures
through
1
1.
Take off cover
2.
Insert cable tie for cable
3a
Standard mounting on standard rail TH 35-7.5
1.
Mount standard rails.
2.
Attach Web server to standard rails.
3.
Press until Web server clicks in place.
3b
Screw on mounting on a level wall
Drill two holes for the screws max. 3.5 mm.
1.
2.
Tighten Web server.
- Make sure the unit is flat (i.e. housing is not warped)
- See "Dimensions" for sizes.
Notes
• Must be mounted vertically for > 35 °C ambient temperature
(circulation through ventilation slots).
Wiring
4
8
See Figures
through
1.
Turn off bus device!
2.
Attach LPB/BSB cable to terminal 2 (DB/CL+) and terminal 3
4
(MB/CL-)
3.
Connect potential-free contacts to D1, M, or D2, M as required
4
4.
Tighten cable tie and cut off the remainder
5.
Break out the notch from the cover
7
6.
Replace the cover
7.
Connect Web server to power
The Web server is operational, when the ON LED is green or
orange.
Display and operating elements
9
See Figure
LED displays
1 ON
(red/green/orange)
Dark
No power.
Steady red
Web server starting (operating system).
Flashing red
Web server starting (application).
Steady green/orange
Web server operational, "Energy indicator = Green
leaf or Orange leaf".
Flashing green/orange
Web server is connected to the remote access portal
2 LPB/BSB (green)
Dark
No bus power.
Lit
LPB/BSB operational.
Flashing
Communication on LPB/BSB.
3 (LED)
Dark
No function.
4 Fault
(red)
Displays faults from the Web server or the connected bus device:
Dark
No fault.
Lit
Acknowledged fault.
Flashing
Unacknowledged fault
5 Quick commissioning (red/green)
Dark
Normal operating mode
Flashing green Quick commissioning active
Steady green
(10 s) device 0.1 or 1 is connected
Steady red
(10 s) device 0.1 or 1 is not connected
Siemens Building Technologies
2
5
6
.
8
+
Operating buttons
The following applies when pressing the buttons:
Short:
<2 seconds.
Long:
<6 seconds.
6 Remote
Short
No function.
Long
Sends system report to the configured fault e-mail
receivers; see as well "Button combination".
7 Service button
Short
State querry for device 0.1 (LPB) or 1 (BSB).
Long
Quick commissioning for first device.
Button combination
Short
No function.
Long
Reestablishes default state.
Note on "default state":
• All configuration data and settings are reset.
• The device list, plant diagrams, and unsent messages are deleted.
• History data is not deleted.
Commissioning
8
See Figures
through
Caution
• Web server connects automatically to the remote access portal as
soon as it has internet access via the Ethernet interface.
• Commissioning guide A6V101022140_en--_b has information on
the remote access portal (www.siemens.com/btproduct?oci670).
• Disabling the automatic connection to the portal and commissioning
without the portal is described in commissioning guide
A6V101022140_en--_b.
Prerequisites
• Web server is mounted, wired, and connected to the Internet via the
Ethernet interface.
• The connected bus device is commissioned.
• The bus device has a valid LPB/BSB address and is operational.
• Bus power supply to the LPB/BSB bus is turned on.
• Recommendation: The bus device is clock slave and set remotely.
• Operating voltage for the web server is switched on.
The web server is ready as soon as the On LED is green or orange.
• PC/Laptop has the same or other Internet access.
A5W00027977 A
A6V101022113_----_b
and
9
2018-04-09
en 7 / 8