Descargar Imprimir esta página

Moeller DS4-340-2K2-M Instrucciones De Montaje página 3

Publicidad

Soft Starter
Type
DS4-340-2K2-M
Input
U
e
24 V g15 % DC / 110 - 240 V g15 % AC 50/60 Hz
U
c
Output
0 - U
Product standard
IEC/EN 60947-4-2
Load-Cycle
11 A: AC-51: 1.5 - 1 : 99 - 600
6 A: AC-53a: 6 - 0.5 : 99 - 600
6 A: AC-53a: 6 - 5 : 99 - 20
Standard Motor
2.2 kW (400 V, 50 Hz, 1500 min
Soft Starter
Type
DS4-340-7K5-MX
Input
U
e
24 V g15 % DC / 110 - 240 V g15 % AC 50/60 Hz
U
c
Output
0 - U
Product standard
IEC/EN 60947-4-2
Load-Cycle
16 A: AC-53a: 3 - 5 : 99 - 10
Standard Motor
7.5 kW (400 V, 50 Hz, 1500 min
Soft Start AC-53a (IEC 947-4-2)
6A: AC-53a: 6 - 5 : 99 - 20
I
I
LRP
I
e
t
t
T
B
P
x
T
+ t
x
B
F =
x 100 %
T
+ t
+ t
x
B
P
I
LRP
X =
I
e
I
= 6 x 6 A = 36 A
LRP
Überlaststrom-Profil/Overload current profile/Profil de courant de surcharge/
Profilato della corrente di sovraccarico/Perfil de corriente de sobrecarga/
2
2
I
t = (X I
)
x T
e
x
2
2
I
t = (6 x 6 A)
x 5 s = 6480 A
Emergency On Call Service: Local representative (http://www.moeller.net/address) or +49 (0) 180 5 223822 (de, en)
DS4-340-2K2-MR
110 - 500 V g10 % AC 50/60 Hz
V AC 50/60 Hz
e
-1
)
DS4-340-7K5-MXR
110 - 500 V g10 % AC 50/60 Hz
V AC 50/60 Hz
e
-1
)
S
S = Starts pro Stunde – Starts per hour
F [%]
F = Lastarbeitszyklus – On Load duty cycle
T
= Startzeit – Start time
T
[s]
x
x
X = Startstrom – Start current ratio
I
= Bemessungsbetriebsstrom – Full load current (FLC)
X
e
I
= Motorstillstandsstrom – Prospective locked motor current
LRP
I
[A]
e
1 h
2
s
DS4-340-2K2-MR-DC
24 V g15 % DC
U
c
DS4-340-11K-MX
DS4-340-11K-MXR
23 A: AC-53a: 3 - 5 : 99 - 10
11 kW (400 V, 50 Hz, 1500 min
t
过载电流曲线图
/
режим перегрузки
-1
)
3/11