VAS6746B
7
Initial start-up
7.1
Setting up and switching on
1. Wheel the AirConServiceCenter to the workplace and lock the front
wheels (10).
I
NOTE
During operation, the device must be on a horizontal, flat surface so that
measurements can be made correctly.
2. Connect the AirConServiceCenter to the mains.
3. To switch it on, set the main switch (22) to I.
The software version number appears in the display (7) for several
seconds:
"SW": Software status
"DB": Database
"SN": Series number
"LF": Language file
✓ The AirConServiceCenter then runs a software test.
✓ When the start-up procedure is complete, the AirConServiceCenter
displays the following:
EN
Dometic WAECO
VAS6746B
SW
DB
SN: 000123
LF
Software test.
Please wait
Refrigerant
PAG oil
UV tracer
11:56:35
V4250148
lhd10026
R1340061
g.
4820
ml
375
ml
313
10/03/17
Initial start-up
69