2.2 HOURMETER

The Hourmeter tracks hours of operation for scheduled
maintenance:
There will be a one time break in "CHG OIL" message that flashes
with the elapsed time in hours and tenths after the first 30 hours
of operation.
This message will actually begin flashing at 29 hours and disable
itself at 31 hours providing a two hour window to perform the
service.
There will be a subsequent "CHG OIL" message every 100 hours.
The message will flash one hour before and one hour after each
100 hour interval, again providing a two hour window to perform
service.
Every 200 hours the "SVC" icon on the lower left hand corner of
the display will flash. The message will flash one hour before and
one hour after each 200 hour interval providing a two hour window
to perform service.
When the hour meter is in the Flash Alert mode, the maintenance
message will always alternate with elapsed time in hours and
tenths. The hours will flash four times, then alternate with the
maintenance message four times until the meter resets itself.
30 hours - CHG OIL — Break-in Interval (First 30 hrs only)
100 hours - CHG OIL — Oil Change Interval (Every 100 hrs)
200 hours - SVC — Air Filter Interval (Every 200 hrs)

2.3 CORD SETS AND CONNECTION PLUGS

2.3.1 120 VAC, 20 AMP, GFCI DUPLEX RECEPTACLE

This is a 120 Volt outlet protected against overload by a 20 Amp
push-to-reset circuit breaker (Figure 7). Use each socket to power
120 Volt AC, single phase, 60 Hz electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than
15 feet long, to prevent voltage drop and possible overheating of
wires.
Figure 7 - 120 Volt AC, 20 Amp, GFCI Duplex Receptacle
6
Section 2 – Operation
Portable Generator System

2.3.2 120/240 VAC, 30 AMP RECEPTACLE

Use a NEMA L14-30 plug with this receptacle (rotate to lock/
unlock). Connect a suitable 4-wire grounded cord set to the plug
and to the desired load. The cord set should be rated for 250 Volts
AC at 30 Amps (or greater) (Figure 8).
Figure 8 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase
loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or
240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts
(7.2 kW) of power. The outlet is protected by either a 30 Amp
(8.0kW) circuit breaker.

2.4 HOW TO USE THE GENERATOR

If there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
Never operate in an enclosed area or indoors!
NEVER use in the home, or in partly enclosed
areas such as garages, even if doors and
windows are open! ONLY use outdoors and far
from open windows, doors, vents, and in an
area that will not accumulate deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which can you cannot see or smell.
This poisonous gas, if breathed in sufficient
concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or permit
even partial blockage of ventilation provisions,
as this can seriously affect safe operation
of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly
maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.