1.
Test the detector at the point of time you feel the lamp needs to
be switched on.
2.
Turn the LUX knob fully clockwise; turn the TIME knob fully anti-
clockwise.
3.
Switch on the power. The detector needs a warm-up time of
± 30 seconds before it will switch on the connected lamp. When
no signal is detected, the lamp will switch off after
± 10 seconds.
4.
Turn the LUX knob fully anti-clockwise. The lamp should switch
off.
4.5
Setting the Detector
1.
Turn the LUX knob until the lamp switches on.
2.
Now, set the switch-off delay with the TIME knob going from
± 10 seconds to ± 15 minutes.
3.
Close the detector with the cover and tighten the screw.
5.
Cleaning and Maintenance
The detector does not need any particular maintenance. However,
occasionally wipe it with a damp cloth to keep it looking new. Do not
use harsh chemicals, cleaning solvents or strong detergents.
6.
Technical Specifications
power supply ................................. 220-240 VAC, 50 Hz
detection range ............................................. 6 m max.
detection angle .................................................... 360°
ambient light......................... < 3 - 2000 lux (adjustable)
installation height .......................................... 2.2 - 4 m
power consumption ..........................................± 0.5 W
motion speed detection .............................. 0.6 - 1.5 m/s
working temperature ........................... -20 °C to + 40 °C
working humidity ......................................... < 93% RH
max. rated load
resistive ..................................... 2000 W (230 VAC)
inductive .................................... 1000 W (230 VAC)