6 STANDARD PROGRAMMING
1 Power Supply
Give power supply, the display shows the following symbols "
*
If the control panel has already been programmed and the power fails or is switched off - once power is returned and a START command
is given, the position reset procedure is performed (see "rESP" in the table "WORKING STATUS MESSAGES" on page 39.
2 Visualisation of inputs and operations-counter status
1. Press the
key for 15 seconds;
2. The display will show respectively:
Inputs status (check it's correct);
Total operations counter (* see P064):
i.g.:
= 3x100* = 3000 operations performed
Maintenance operations-counter (* see P065):
i.g.:
= 5*x500 = 2500 operations remaining be-
fore the maintenance intervention request (
noeuvres-counter disabled)
3. Hold down the
key to display a cyclic 3 options, or rele-
ase the
button to exit the parameter.
3 Selection type of operators
1. Scroll down the parameters with
lise P028;
2. Access the parameter by pressing the
3. Acting on
and
keys, set:
Type 00
Type 01
• 005 5/24
• 000 Geko - An-
• 006 8/24
golo
• 007 Gulliver - Rev
• 001 Look - Mac
• 002 Ghost
• 003 Livi 500 -
502 - 550PL
Warning: If you are using non DEA System operators, set the parame-
ter on the closer value for family type and performances (refer to table
on page 26).
4. Confirm your choice by pressing the
to P028).
", "
= ma-
! IMPORTANT !
and
keys until you visua-
key;
Type 02
Type 03
• 003 Livi 902/24 -
• 003 Pass
905/24
• 004 Stop
key (display returns again
", "
" (or the Type selected) and then "- - - - ".