3. Features
Power Strip (PDU3V20D354, PDU3V20D354A, PDU3V20D354B)
2
10
ATS Automatic Transfer Switch
(PDU330AT6L2130, PDU330AT6L1530, PDU350AT6H50)
10
A
3
1
Power Strip Outlets: These single-phase IEC C13 outlets receive power from the interlaced
3-phase power input connections of Source A or Source B of the ATS. These outlets are not
controllable.
2
Power Strip Input Power Cord: The 7-conductor cord has an
8-position connector that attaches directly to the ATS.
3
ATS Source A and Source B Input: The cords are permanently
attached to the ATS and have L15-30P , L21-30P and Hubbell
CS8365C plugs.
4
Digital Display: Shows source status, measured values, display
modes and other information. See the Digital Display section
for detailed explanations of the indicators and displays.
5
SNMP Reset Button: Press the reset button for 3 seconds to
reboot the ATS network card. Rebooting the network card will
not erase network settings or interrupt AC power. The reset
button is recessed. Use a paper clip or other suitable object to
press it.