Technical Data
Type
Power supply
Nominal force
Input power
Nominal stroke length*
Running speed:
O1, O2
O3
C3
C2, C1
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Ambient humidity
Emission sound pressure level
Additional functions*
ACB interface
Opening and Closing Ranges
O1*
23 mm
200 N
C1*
C2*
23 mm
77 mm
150 N
150 N
* Programmable with software SCS ** + approx. 20 % switch-off reserve (temporary)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges C3 and C2, the drive
runs "OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range C2
and C1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
6/16
VCD 204-5-ACB-M
VCD-0204-0250-5-ACB
230 V AC, +10 % / -15 %, 50 Hz
200 N**
22 W / 30 VA
250 mm ± 2 %
6 mm/s
5 mm/s
6 mm/s
5 mm/s
approx. 2000 N (Excluding bracket)
>20.000 double strokes
30 % (With cycle time 10 minutes)
Zinc-diecasting powdercoated (~ RAL 9006)
IP 30
0 ... +60 °C
≤ 90 %, not condensing
LpA ≤ 46 dB(A)
Closing edge protection = activated (3 repetitions of stroke);
Locking relief = activated (retraction lift max. 0,2 mm)
Modbus RTU / RS 485, 19.200 bps, 8 data bits, 1 stop bit, parity: even
O2*
200 N
English
VCD-0204-0350-5-ACB
350 mm ± 2 %
C3*
200 N
99.827.75 1.1/08/19
O3*
15 mm
200 N