Continue programming accordingly to set the temperature mode and
switching point time for the selected switching point until all switching points
are set.
Example 1
C
comf mode
E
eco mode
This example describes the following programme:
SP
time
1
6:00-8:00
2
8:00-12:00
3
12:00-14:00
4
14:00-18:00
5
18:00-22:00
6
22:00-6:00
8.3 Temporarily Modifying the Temperature
Modifying the programmed temperature is simple: just rotate the dial to the
desired temperature. The thermostat will maintain the temperature until the
next switching point.
8.4 Group Execution Priority
By default, single-day groups have priority over multi-day groups. In other
words, if a single-day group is programmed differently than a multi-group,
the thermostat will follow the single-day group's settings.
Note that modifying a setting in a multi-day group will automatically alter
the setting in the coinciding single-day group.
V. 01 – 22/06/2016
DRT1
SP
temperature
20 °C (comf mode 1)
13 °C (eco mode 1)
20 °C (comf mode 1)
13 °C (eco mode 1)
24 °C (comf mode 2)
16 °C (eco mode 2)
9
switching point
H
heating