Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SYMBOLS
FUEL WARNING
No smoking when filling
with gasoline. Do not
overfill. Full level is 1 in.
below the top of the fuel
neck. Stop the engine
for five minutes before
refueling to avoid the
heat from the muffler
igniting fuel vapors.
ENGINE LUBRICANT
WARNING
You must add lubricant before first
operating the generator. The oil reser-
voir capacity is 1.1 qt. Always check
the lubricant level before each opera-
tion. The lubricant level should always
register between the hatched areas on the dipstick. The unit
is equipped with a sensor which will automatically shut off
the engine if the lubricant level falls below a safe limit.
GROUNDING WARNING
National Electric Code requires generator to be grounded to
an approved earth ground.

ELECTRICAL

EXTENSION CORD CABLE SIZE
Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load.
Inadequate size cables can cause a voltage drop, which can damage the appliance and overheat the cord.
Load in Watts
Current in
Amperes
At 120V
2.5
300
5
600
7.5
900
10
1200
15
1800
20
2400
25
3000
30
3600
40
4800
At 240V
#8 Wire
600
1200
1800
2400
3600
4800
175 ft.
6000
150 ft.
7200
125 ft.
9600
90 ft.
7 — English
Maximum Allowable Cord Length
#10 Wire
#12 Wire
1000 ft.
600 ft.
500 ft.
300 ft.
350 ft.
200 ft.
250 ft.
150 ft.
150 ft.
100 ft.
125 ft.
75 ft.
100 ft.
65 ft.
#14 Wire
#16 Wire
375 ft.
250 ft.
200 ft.
125 ft.
125 ft.
100 ft.
100 ft.
50 ft.
65 ft.

Publicidad

Tabla de contenido
loading

Tabla de contenido