4. SAFETY

This product conforms to the latest directives
concerning safety and electromagnetic compatibility.
European Low Voltage Directives 73/23/EEC and
93/68/EEC
European EMC Directives 89/336/EEC and
93/68/EEC
Safety Standards
BSEN61010-1: 1993. General Requirements.
Safety requirements for electrical equipment for
measurement, control and laboratory use.
BSEN61010-2-032: 1995. Particular requirements for
hand held current clamps for electrical measurement
and test.
EMC Standards
RF Susceptibility
EN50082-1: 1992 3V/m Residential, Commercial and
Light Industry
RF Emissions
EN50081-1: 1992 Residential, Commercial
and Light Industry
FCC Part 15 Class B
This product is designed to be safe under the following
conditions:
− indoor use
− altitude up to 2000m
− temperature 0°C to +50°C
− maximum relative humidity 80% for
temperatures up to 31°C decreasing linearly
to 40% relative humidity at 50°C.
Use of the meter on uninsulated conductors is limited
to 300V RMS or DC and frequencies below 1kHz.
This meter complies with the requirements of the above
safety standard for 300V Cat III Pollution degree 2
Safety in its use is the responsibility of the operator who
must be a suitably qualified or authorised person.
Users of this equipment and or their employees are
reminded that Health and Safety Legislation require
them to carry out valid risk assessments of all electrical
work so as to identify potential sources of electrical
danger and risk of electrical injury such as from
inadvertent short circuits.