Vega 650 Handbook
Pollution Degree
Overvoltage Category
Class
Weight
IP Rating
* 3000m for 60601-1 2nd ed, IEC inlet and cooling options D and E.
** Option "I" can not be vertical with the inlet face accessible.
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth - 2.25 - 2.35kVDC
Primary mains circuits to transformer core - 4.25 - 4.35kVDC**
Primary mains circuits to secondary -4.25 - 4.35kVDC**
Outputs to each other and to earth are isolated to 200VDC.
**This test is not possible with Y capacitors fitted to the unit as damage to these capacitors may occur. It is also
necessary to short circuit the outputs together and to earth
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
UL/CSA62368-1 UL Recognised. C-UL for Canada
IEC / EN60950-1 - CE mark.
IEC/EN60950-1, IEC/EN62368-1, IEC/EN 61010-1 and IEC/EN60601-1 - CB Report and Certificate.
CE marking when applied to any Vega 650 product indicates compliance with the Low Voltage Directive in that it
complies with EN60950-1 and with the ROHS Directive.
UL/CSA 61010-1 : UL + C–UL approval
UL/CSA 60601-1: UL + C–UL approval
Fusing: Internal fuse (FS1) 16A/250V fast acting HBC fuse 6.3x32mm.
Symbols:
AC
EARTH
N
Fast-ons
If the earth terminal of the Vega 650 PSU is connected to the main incoming earth conductor of the end equipment,
the installer must cover the earth symbol with a label bearing the earth symbol of IEC60417-5019.
Note: All output voltages/variants may not be available as standard units, refer to datasheet for standard
product range. These (and other variants) may be available as non-standard or custom units, please contact
our sales team for details.
N – Neutral
L
2
II
I
2 kg (Dependent on configuration)
IPX0
L – Live
N
L
Terminal block
Page 14 of 35
17137 issue 37, Sept 2019