Fan; Arc Detection - Fronius Galvo 2.5-1 208-240 Manual De Instrucciones

Ocultar thumbs Ver también para Galvo 2.5-1 208-240:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

E-meter calibration
Specification of a correction value so that the data shown on the inverter display corre-
spond to the calibrated data shown on the electric meter
Unit
Setting range
Factory setting
Currency
Currency setting
Setting range
Feed-in tariff
Charge rate setting for the energy fed into the grid
Setting range
Factory setting

Fan

for checking the fan functionality
Setting range
-
-
-

Arc Detection

for checking arc detection/interruption
Setting range
Arc.det. Status
displays the current status of arc detection/interruption
Start Self-test
self-test to check whether the inverter interrupts grid power feed operation when an arc
is detected.
Test procedure:
The self-test starts. The arc detection/interruption function simulates an arc and sends
the corresponding signal to the inverter.
If the test is successful, the inverter disconnects from the grid and stops grid power feed
operation.
The message "Self-test completed and Start AFCI" is shown on the display.
30
Use the "Up" and "Down" keys to select the desired fan
Press the "Enter" key to start testing the selected fan
The fan runs until the menu is exited by pressing the "Esc" key
Select "Arc Detection" in the Setup menu
1
Press the "Enter" key
2
Use the up and down keys to select "Start Self-test"
3
Press the "Enter" key
4
Confirm the indication by pressing the "Enter" key
5
%
-5.0 to +5.0
0
3-digit, A-Z
2-digit, 3 decimal places
(depends on the country setup)
Test fan 1 / Test fan 2 (depends on device)
ArcDetector Status/Start Self-test