Fronius Galvo
Input data
Recommended PV power
MPP voltage range
Initial voltage
Max. input voltage
at 1000 W/m² / 57.2°F (14 °C) in an open circuit
Nominal input voltage
Nominal input current
Max. input current
Max. short circuit current of the solar modules
Max. backfeed current
Output data
Nominal output power (P
nom
P
at +122°F (50°C)
nom
Max. output power
Nominal mains voltage
Mains voltage tolerance
Operating AC voltage range
Grid voltage setting range
Voltage limit accuracy
Voltage limit clearing times setting
range
Nominal output current
Number of phases
Maximum continuous utility backfeed
3)
current
Synchronization in-rush current
Maximum output fault current / duration at 208 V
Nominal output frequency
Output frequency range
Setting range for grid frequency
Frequency limit accuracy
Frequency clearing times setting range
Total harmonic distortion
)
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
3)
at 220 V
at 240 V
2.5-1 208-240
3.1-1 208-240
2.0 – 3.25 kWp
2.5 - 4.0 kWp
165 – 440 V DC
185 V
1)
550 V DC
330 V
8.0 A
10.0 A
16.1 A
20.0 A
20.1 A
25.0 A
8.9 A
13.4 A
2500 W
2930 W
2500 W
3100 W
2500 W
3100 W
2500 W
2600 W
2500 W
2650 W
2500 W
2750 W
2500 W
3100 W
208 V / 220 V / 240 V
-12 % / +10 %
183 - 229 V
194 - 242 V
211 - 264 V
104 - 288 V
104 - 288 V
104 - 288 V
1% of nominal value
2)
0,016 - 21,0 s
12.0 A AC
14.1 A AC
11.4 A AC
14.1 A AC
10.4 A AC
12.9 A AC
2
0 A
36.0 A / 9.4 ms
456 A / 1.9 ms
440 A / 1.5 ms
488 A / 1.4 ms
60 Hz
45.0 - 65.0 Hz
45.0 - 65.0 Hz
0.05 Hz
2)
0.016 - 600 s
< 4 %
49