Or a fixed electrical terminal. In this case, the
-
installation must be fitted with an omnipolar
disconnect device having a contact opening
distance greater than 3 mm.
•
The installation must be in compliance with
NFstandard C 15100. In particular, the installation
must be properly grounded (green and yellow
wire).
3.7 - Walls in the vicinity of the appliance
Install the fireplace ready to set up at a minimum 300
mm
distance
from
accommodation and from any combustible material.
The appliance should be installed on a fire-proof floor.
In order to protect the floor from heat radiation and
possible falling combustible, install the unit on
reflective metal shielding (or on a tiled floor) which
covers the entire surface underneath and in front of
the unit.
The apparatus should be installed on a floor with
sufficient bearing capacity. If an existing building does
not meet this precondition, proper measures should
be taken (for example, the installation of a load
spreading plate) to enable the floor to bear the
apparatus.
4 - INSTALLATION OF THE "READY TO INSTALL"
FIREPLACE (Fig. 5 and 6a)
Screws provided (Fig. 6b)
2 installation configurations are possible :
In both cases, the ceiling shield is placed
60 mm from the ceiling.
To remove the knockouts in the various
shields, simply use a ∅ 6 drill bit to overdrill
the ∅ 2 mm marks.
•
CONNECTION ON TOP (FIG 5)
Remove the circular knockouts from the ceiling
and tube cover shields (leave the others in place)
(Fig. 7).
Secure the wall + ceiling shield assembly to the
wall with the 6 screws B, anchors D and nuts C
included
in
the
maintaining a distance of 60 mm between the
ceiling and the ceiling shield (Fig. 9).
Place the fireplace against the wall.
Fit the tube cover shield onto the connecting tube.
Install the connecting tube.
Secure the tube cover shield to the hood shield
using the sheetmetal screws A supplied in the
instruction packet (Fig. 10).
the
side
walls
of
instruction
packet
while
•
CONNECTION AT REAR (FIG 6a)
Remove the circular knockout in the hood shield
and the rectangular knockout in the wall shield.
Leave the others in place (Fig. 8).
Position the fireplace equipped with its connecting
pipe (Fig. 6a).
Slide the wall + ceiling shield assembly into place
(Fig. 9) while maintaining a distance of 60 mm
between the ceiling and the ceiling shield. Locate
the fixation points on the wall.
the
Only for C07342 : locate the fixation points of the
rectangular pre-cut piece (Fig. 11).
Move the fireplace away from the wall slightly. Fit
the horizontal part of the connecting tube (Fig.
11). Replace the fireplace back against the wall.
Fix the wall screen and the ceiling screen.
Only for C07342 : the wall screen should be fitted
with the rectangular pre-cut piece (4 self-tapping
screws A supplied in the instruction packet ; this
operation is performed when the floor to ceiling
height is greater than 2.4 m).
Place the fireplace against the wall.
Fit the connecting tube to the chimney flue.
Secure the tube cover shield to the hood shield
using the self-tapping screws A supplied in the
instruction packet
•
NEXT, IN ALL CASES (FIG. 12) :
Note the dimension H between the top of the
-
hood and the ceiling.
Fit the upper tube cover into the lower tube cover
-
and adjust to dimension H.
Drill four ∅ 3.2 holes in the upper tube cover
-
through the 4 holes located in the upper section
of the lower tube cover.
Assemble the 2 tube covers with the 4 self-
-
tapping screws A included in the instruction
packet.
Spread apart the assembly made of the 2 tube
-
covers and fit the hood onto the fireplace.
Secure this assembly onto the hood using 4 self-
-
tapping screws A, included in the instruction
packet.
Special case where the chimney flue penetrates into
the room at a certain height and whose dimensions
allow its integration into the upper tube cover (see
Fig. 13).
5 - FIREPLACE OPERATION
•
This "closed insert" fireplace is a veritable
heating appliance :
Heigh yield.
-
Long-lasting, reduced burn rate operation.
-