Special Function - Honeywell FocusPRO 5000 Serie Instrucciones Para La Instalación

Ocultar thumbs Ver también para FocusPRO 5000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Setup function
Shaded areas below apply only to
9
Stage 1 compressor
cycle rate (CPH)
10 Stage 2 compressor
cycle rate (CPH)
12 Manual/Auto
changeover
14 Temperature
display
15 Compressor
protection
26 Auxiliary heat control
27 Heat temperature
range stops
28 Cool temperature
range stops

Special function

Auxiliary heat control (Setup Function 26):
Comfort Setting: The thermostat will prioritize comfort over economy
depending on heat pump performance, load conditions and whether the
thermostat is calling for the heat pump. Raising the temperature just a few
degrees will often activate the auxiliary heat.
Economy Setting: The thermostat will attempt to reach the temperature setting
without activating the auxiliary heat. The thermostat will wait to activate the
auxiliary heat depending on heat pump performance, load conditions and how
many degrees the temperature setting is changed.
Settings & options (factory default in bold)
TH5320U/TH5220D
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0
Manual changeover (Heat/Cool/Off)
1
Auto changeover (Heat/Cool/Auto/Off)
2
Auto changeover only (Auto)
0
Fahrenheit
1
Celsius
5
Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
0
Comfort
1
Economy
90
Max. heat temperature setting is 90 °F (32 °C)
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
50
Min. cool temperature setting is 50 °F (10 °C)
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
6
or as otherwise noted.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Focuspro th5320uFocuspro th5220dFocuspro th5110d

Tabla de contenido