TC-Standard (+)
5.3 Using the Digital Interface
The digital interface on this device is a Modbus RTU protocol,
which physically communicates via RS485 (2-wire). The cooler
therefore takes on the role of the slave in communication.
The Modbus interface enables direct access to process and
diagnostic data and parameters during operation.
5.4 Modbus Configuration
The settings below are the defaults; the parameters can be ad-
justed if the interface is enabled.
1 start bit
8 data bits
1 parity bits (configurable)
1 stop bit (*)
Baudrate: 19200 bps (configurable)
Device ID: 10 (configurable)
(*) The length of a Modbus frame is always 11 bit, configuring
the interface at 0 data bits automatically changes the number
of stop bits to 2.
5.5 Modbus Communication
Communication via Modbus RTU is always imitated by the
master (request). The slave (typically) responds to the request
with a response. A Modbus RTU frame for a request/response
always has the following structure:
Address field
Function code
(A)
(FC)
1 byte
1 byte
Register addresses and data are transferred in Big Endian
format.
Every register stands for a 16 bit value, with the information
represented in various data types. The data type and required
function code are assigned to the respective registers in the
following tables.
To read/write data types with sizes larger than an individual
register, multiple registers must be addressed.
Supported function codes:
Function code (FC)
Read Holding Registers
Write Multiple Registers
Data types:
Description
Number of bytes
Float
4
Int16
2
Uint16
2
Int32
4
Uint32
4
BX440017 ◦ 09/2021
Data
CRC
1 ... 252 bytes
2 bytes
FC values
3
16
Number of registers
2
1
1
2
2
6 Maintenance
Always observe the applicable safety- and operating regula-
tions when performing any type of maintenance. Please refer
to the original operator's manual on the included CD or online
at www.buehler-technologies.com for maintenance informa-
tion.
7 Service and Repair
Please refer to the original operator's manual on the included
CD or online at www.buehler-technologies.com for a detailed
description of the unit including information on
troubleshooting and repair.
7.1 Error messages on the display
If an error occurs, the display will read "Err". Press the "
button to show the error number(s).
Error messages will appear until the unit has been restarted
or the error is cleared using the "Func" button. It can only be
cleared if the cause for the error has been corrected.
Causes / Action: The following is a list of the most common
causes and actions for the respective error. If the actions listed
do not resolve the problem, please contact Service.
Problem/malfunc-
Possible cause
tion
No
• No voltage
display
• Loose connect-
ing cable
• Display failure
D1.02
(The software ver-
sion for the display
(perman-
will appear).
ent)
• Not communic-
ating with the
controller
Error
• An error has oc-
curred
Error 01
• Controller mal-
function
Error 03
• Microcontroller
fault / MCP2
Error 04
• EEPROM error
Error 22
• Moisture de-
tector 1 cable
break
Error 32
• Moisture de-
tector 2 cable
break
"
Action
• Check the sup-
ply cable
• Check fuse
• Check connec-
tions
• Check connec-
tions
• Read the error
number as de-
scribed above
• Clear error
(temporary
fault)
• Disconnect
from power for
approx. 5 s
• Contact service
• Contact service
• Contact service
• Check moisture
detector line
• Check moisture
detector
• Check moisture
detector line
• Check moisture
detector
Bühler Technologies GmbH
17