Greenlee 2007 POWER FINDER Manual De Instrucciones página 16

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

An appropriate voltage tester, such as the Greenlee 6706,
6708, or 6709, must be used to verify the absence of voltage.
EXAMPLE 6
Connection for finding a short to ground
1) Turn the tripped breaker to the full off position. (If in a fuse
panel, remove, but do not replace, the blown fuse!)
2) Disconnect the shorted hot wire at its source (the fuse panel,
breaker panel, safety switch, power panel, switchgear, etc.).
3) Using an approved continuity-tester or multimeter, check the
affected wire to ensure that a short-to-ground exists.
4) Using the transmitter adapter plug, connect one alligator clip to
the shorted lead at its connection point in the panel.
Greenlee Textron Inc. / Subsidiary of Textron Inc.
2007 POWER FINDER™ Circuit Tracer
Lockout electric power to any circuit before
connecting or disconnecting. Alert any
persons present of your work. Only you
may restore power!
Failure to lockout power may result in
electrocution or death.
IMPORTANT
16
4455 Boeing Dr., Rockford, IL 61109-2988 USA 815/397-7070

Publicidad

Tabla de contenido
loading

Tabla de contenido