Descargar Imprimir esta página

Dickson TH800 Manual Del Usuario página 6

Publicidad

Alarm Relays (Optional)
The SPST 24V 500mA relay contacts are normally open and will close on alarm conditions when the alarms
are enabled. Relay contacts are always functional when the alarm is enabled. The relay will close only during
minimum and maximum alarm conditions. 2 pen models have two sets of relay contacts which operate
independently.
Dip Switch Set-up
To set-up the TH8 recorder for your specific
application, you might need to change some of
the Dip Switches. The Dip Switches are located on
the back of the unit (figure 3). Use a pen or small
screw driver to flip the switches. Remember to
install correct chart to match corresponding
Dip Switch setting.
Dip Switches for ranges
DICKSON TH8 Dip Switch Settings:
Up = On; Down = Off
For Model
Switches 1 - 6
7 Day
All Models
All Models
24 Hour
31 Day
TH802/03/05
All Models
RH
All Models
Dew Point
-20° to 120°F
All Models
40° to 110°F
TH802/03/05
TH803/05
0° to 200°F
-20° to 50°C
All Models
5° to 40°C
TH802/03/05
Remember to install the correct chart to match
corresponding switch setting
- Addison, Il
Dickson
Note: (TH800) On Dip Switch label -20 to 120°F =
+32 to 120°F and -20 to 50°F = 0 to 50°C
Recording Time
The TH8 recorder has three/two different recording
time options
24 hour
7 day
31 day (TH802/03/05)
NOTE: Remember to install correct chart to match
corresponding switch setting.
Rev. 01/09
1 2 3 4 5 6
D
D
D
U
U
U
D
U
D
D
D
D
D
U
D
U
U
U
D
D
U
U
D
www.dicksondata.com
#1 down
#2 up
#1 down
#2 down
#1 up
#2 up
Dip Switch 7 & 8 are not active on this recorder.
Slide toggle up for on position.
1
2
3
4
Slide toggle down for off position.
Temperature Range
The TH8 will record up to 5 temperature ranges
(depended on model). Dip switch #3, #4, & #5
allows you to select the temperature range.
-20 to +120°F
+40 to +110°F
-20 to +50°C
+5 to +40°C
0 - 200°F
RH/Dew Point
Dip switch #6 allows you to select whether RH or
dew point is recorded by the blue pen and shown
on the display for the models with displays. (The
red pen always records temperature.)
RH
Dew Point
NOTE: When the blue pen is recording dew point,
the reading indicates the temperature at which
dew will form or frost point, so you should use the
temperature scale on the chart to read dew point.
5
6
7
8
#3 down
#4 down
#5 down
#3 down
#4 down
#5 up
#3 up
#4 down
#5 down
#3 up
#4 up
#5 down
#3 down
#4 up
#5 up
#6 down
#6 up

Publicidad

loading

Productos relacionados para Dickson TH800

Este manual también es adecuado para: