Fan-Control Adjustment; Position Of Electrodes; Ionisation Current - baltur BPM 10 EVO Manual De Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FAN-CONTROL ADJUSTMENT

LME ...

POSITION OF ELECTRODES

Position of potentiometers
P1
1
stage Thermal Output adjustment
st
P2
Ignition Thermal Output adjustment
P3
2
stage Thermal Output adjustment
nd

IONISATION CURRENT

The minimum current needed to run the equipment is 1.5 µA. The
burner provides a significantly higher current and therefore does not
normally require any checks at all. Should however, the ionisation
current need to be measured, a microammeter must be connected
in series to the ionisation electrode lead.
8 / 10
0006160031_201307

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bpm 40 evo

Tabla de contenido