OPERATING ANOMALY

ANOMALY
The burner does not start.
SOLUTION
Check the supply voltage;
Check the regulation thermostat (TC);
Check that the connectors are properly inserted.
Check that the network fuse is intact.
Check the gas inlet pressure (2);
Press the reset key (1)
Check the gas valve opening; if the valve does not open a
pressure drop will occur in point (2);
Check the ignition electrodes (3);
Check that there is no ionisation current.
ANOMALY
The burner ignites, the ionisation current is present but after the
safety time the burner turns off.
SOLUTION
Check that the phase and neutral positions have been respected.