⑰ Heating thermo-OFF temp adjustment
⑱ Return air sensor adjustment
⑲ Fan control in cooling thermo-OFF
⑳ Fan control in heating thermo-OFF
⑰ Heating thermo-OFF temp adjustment
Adjust the temperature for judging to make thermostat ON or OFF during
heating operation.
Adjustable range is 0°C to +3°C.
⑱ Return air sensor adjustment
Adjust the temperature detected with the return air temp sensor.
Adjustable range is -2°C to +2°C.
⑲ Fan control in cooling thermo-OFF
Set the fan speed at the cooling thermo-OFF.
Low:
The fan runs at the low speed.
Set fan speed: The fan runs at the same speed as that during the thermo-ON
operation.
Intermittent:
Cycles of Lo fan operation for 2 minutes and stop for 5 minutes
are repeated.
Stop:
The fan is stopped.
⑳ Fan control in heating thermo-OFF
Set the fan speed at the heating thermo-OFF.
Low:
The fan runs at the low speed.
Set fan speed: The fan runs at the same speed as that during the thermo-ON
operation.
Intermittent:
Cycles of Lo fan operation for 2 minutes and stop for 5 minutes
are repeated.
Stop:
The fan is stopped.
— 30 —