10. Compressor
10.1 Compressor on and off control specifications
1.1 When one of the following conditions is met, the compressor stops:
1) Measured temperature in freezer room ≤ Shutdown temperature of freezer room
2) Enter defrosting cycle
3) The compressor runs continuously for more than 3 hours, will stop at least 5 minutes
1.2 When all the following conditions are met, the compressor starts up:
1) Measured temperature in freezer room ≥ Start up temperature of freezer, or when refrigerator is set to forced
cooling mode or fast cooling or fast freezing mode
2) Compressor shutdown time has been more than 5 min
· When 1.1 and 1.2 are not satisfied, the compressor maintains the original state