2-wire
PE +
-
N
L
AC: terminal 1: L
terminal 2: N
19 to 230 V AC, + 10 %,
50 to 60 Hz, 1.5 VA
DC: terminal 1: +
terminal 2: -
19 to 230 V DC, + 10 %, 1 W
Sensitivity
If the measured material tends to cake or build up, the sensitivity adjustment switch can
be set to position A to decrease the sensitivity of the probe (factory setting is position B).
The sensitivity for interface applications should be set to position B, while the setting for
high-flow applications should be position A.
Page EN-12
SITRANS LVS200 – INSTRUCTION MANUAL
All manuals and user guides at all-guides.com
NAMUR IEC 60947-5-6 8/16 mA or 4 to 20 mA
PE + -
ca. 7 to 9 V DC,
intrinsically safe
(IEC 60947-5-6)
PE + -
DC: terminal 1: +
terminal 2: -
12.5 to 36 V DC, + 0 %
FSH/FSL adjustment or
High/Low Alarm setting (NAMUR)
sensitivity adjustment:
B = factory setting
A = decreased sensitivity
7ML19985FT62