All manuals and user guides at all-guides.com
2.1 Diagnosis / display status LEDs
AS−i
Fault
(green)
(red)
on
out
on
flashes
on
on
flashes
flashes
flashes
on
out
out
AUX/PWR (green)
on
out
Inputs (yellow)
on
out
Note
The AS−Interface has an integrated watchdog function
which resets the outputs (solenoid coils) when the bus
communication fails.
Festo VTSA−ASI−...−4E4A−Z 0802NH English
Meaning
AS−Interface voltage applied, no fault
Short circuit/overload at input
Bus communication failed (Watchdog expired)
Additional power supply not applied or
undervoltage (possibly valves do not switch),
periphery fault
AS−Interface address not set (= 0)
AS−Interface voltage not applied
Meaning
Additional supply exists
No additional supply or additional supply failed
Meaning
1−signal at input
0−signal at input
19