How To Set The Fan Speed - Toshiba TCB-AX21U-E Manual Del Propietário

Control remoto para el aparato de aire acondicionado (tipo split)
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 60

HOW TO SET THE FAN SPEED

When installing a 4-way cassette type indoor unit to high ceiling of a room, the fan motor speed
can be selected in agreement with height of the ceiling and numbers of the discharge port.
For details, refer to the Installation Manual for 4-way discharge cassette type unit.
Setup
Tap 1
Tap 2
No.
OFF
OFF
(0)
Setting at shipment
(1)
OFF
ON
(3)
ON
OFF
The fan motor speed is selected by Dip switch [S003] on the sensor P .C. board inside or the
adjust corner cap (including sensors) of the ceiling panel of 4-way discharge cassette type
indoor unit.
Screw
• After selecting a fan motor speed, reassemble the ceiling panel as before.
Using a clamper, fix the cable connectors with screws.
All manuals and user guides at all-guides.com
Installable ceiling height (Unit: m)
RAV-SM560UT-E
4-ways 3-ways 2-ways 4-ways 3-ways 2-ways 4-ways 3-ways 2-ways
2.8
3.2
3.5
3.2
3.5
3.8
3.5
3.8
Clamper
Sensors cover
Dip switch [S003]
1
Used in [Trial operation]
2
Tap 1
3
Used by selecting [Priority/Secondary]
4
Tap 2
4
RAV-SM800UT-E
3.0
3.3
3.6
3.3
3.5
3.8
3.6
3.8
Sensor P.C. board
Adjust corner cap
ON
4
3
2 1
RAV-SM1120UT-E
RAV-SM1400UT-E
3.6
3.9
4.2
3.9
4.1
4.3
4.2
4.3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tcb-ax21u w-e

Tabla de contenido