Tabla De Contenido; General Description; Electrical Data; Installation - Grundfos SM 111 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 25
All manuals and user guides at all-guides.com
English (GB) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
Warning
Prior to installation, read these
installation and operating instructions.
Installation and operation must comply
with local regulations and accepted
codes of good practice.

1. General description

The SM 111 is used for the collection and transfer of
sensor data. The SM 111 works together with the
IO 111* as shown below.
IO 111
Power line
communication
using Grundfos
protocol
ON
DIP
1 2 3 4 5 6 7 8 9 10
Fig. 1
IO 111 and SM 111
* Only IO 111 versions with communication module,
part number 96177804.
The SM 111 can collect data from
Page
7
7
7
7
7
8

2. Electrical data

8
8
Supply voltage:
8
Supply current:
8
Power consumption:
8
Ambient temperature:
8
Enclosure class:
9
9

3. Installation

The SM 111 must only be installed by Grundfos or an
authorized service workshop.

3.1 Electrical connection

Before installation, check that the SM 111 has not
been damaged during transportation.

3.2 EMC-correct installation

It is especially important to ensure an EMC-correct
installation of pumps with frequency converter.
The following rules must be observed:
1 2 3 4 5 6 7 8 9 1011 1213 14
Sensor inputs
2 current sensors, 4-20 mA
1 water-in-oil sensor
3 Pt100 thermal sensors
1 Pt1000 thermal sensor
1 PTC thermal sensor
(maximum 3 PTC sensors in series)
(According to DIN 44081/44082)
1 digital input.
14 VDC ± 1 VDC
210 mA rms/320 mA peak
5 W
0 °C to 65 °C
IP22
Connect the cable screen to earth.
Do not twist screen ends, as this will destroy the
screen effect at high frequencies. Use cable
clamps as shown in fig. 2.
It is important to ensure a good electric contact
from the mounting plate through the mounting
screws to the metal cabinet of the frequency
converter.
Use toothed washers and a galvanically
conducting mounting plate.
Note the insulating plastic
layer between screen and
sheath.
Fig. 2
Screen fixed with cable clamp
7

Publicidad

Tabla de contenido
loading