Remote Module Led Status Indicators - Briggs & Stratton Dual 200 Amp Manual Del Usuario

Ocultar thumbs Ver también para Dual 200 Amp:
Tabla de contenido

Publicidad

Remote Module LED Status Indicators

Symphony II System does not communicate or manage appliances/
loads when utility power is present.
NOTICE When looking at LED's, make sure you look straight on
and not at an angle.
Low Voltage (Single and Dual) Modules
A
B
C
A - Low Voltage Control Wiring Terminal Contacts
B - Priority Selector
C - Power/Line Connection
D - Neutral Connection
E - Transparent, plastic cover
F - Ground Connection (optional)
G - Status LED
H - Plastic Barrier
Status LED(G) is used to indicate communication status.
Utility power present:
• Normal State
-
Generator power present:
• Normal State
-
Utility State Problem (see Troubleshooting):
-
H
-
-
G
Generator State Problem (see Troubleshooting):
-
F
-
-
D
E
Orange LED - No communication and appliances/loads
cannot be managed by Symphony II System
Green LED - Signal communication detected and
appliances/loads can be managed after 5 minute delay
No LED - No power to low voltage control board; verify
correct wiring
Green LED - Low voltage, not functioning; replace low
voltage module
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
No LED - No power to low voltage control board; verify
correct wiring
Orange LED - Signal communication not detected; verify
correct wiring
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
21

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Split 400 amp071057

Tabla de contenido