Briggs & Stratton 076180 Manual De Instalación Y Arranque página 15

Sistemas de generador de reserva
Ocultar thumbs Ver también para 076180:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Typical Installations with Structure Without a Fire Rating
NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend.
5 ft (1.5 m) min.
Standby
Exhaust
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
Exhaust
A
Legend for Generator Locations to reduce the risk of fire.
Standby weatherproof enclosure must be at least 5
A
ft (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in
height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from
any structure, shrubs, trees or any kind of vegetation.
A
B
A
B
A
B
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
5 ft (1.5 m) min.
A
B
Standby weatherproof enclosure must have a minimum
C
of 5 feet (1.5 m) overhead clearance from any
structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
A
5 ft (1.5 m) min.
Standby
Exhaust
A
Exhaust
15

Publicidad

Tabla de contenido
loading

Tabla de contenido