Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 59
30RHX

Data

Table IV: Control and safety device settings
Freeze-up protection
Compressor first start delay
Compressor start delay
(OFF-ON)
Compressor anti-cycling protection
(OFF-ON)
*
When the compressor start delay has elapsed, the unit automatically restarts, if the
leaving water temperature is above 2.7°C.
Table V: Water flow / System water content
Unit
30 RHX
Water flow
l/s
Nominal
System water content
l
Maximum operating pressure
Charge pressure
before operation
Table VI: Water content copper piping
Diameter-mm
outside
14
16
18
22
28
35
Table VII: Water content steel piping
Diameter
outside
inches
3/8 Gas
1/2 Gas
3/4 Gas
1 Gas
GB - 4
All manuals and user guides at all-guides.com
open
closed
°C
2,7
*
sec
60
sec
90
cycle/h
12
Mod.
006
008
011
015
0,32
0,44
0,57
0,76
Min.
24
31
36
48
kPa
300
300
300
300
kPa
120
120
120
120
inside
litres / metre
12
0.11
14
0.15
16
0.20
20
0.31
25
0.49
32
0.80
inside
litres / metre
mm
12.7
0.13
16.3
0.21
21.7
0.37
27.4
0.59
Table VIII: Operating limits
Power supply :
230 - 1 - 50
400 - 3 - 50
* ATTENTION:
For outside temperatures below 0° C, mix the correct amount of
antifreeze with the water.
Operating range - cooling
Maximum water temperature at start-up (LWT) 35 °C max.
18
15
10
4
-15 -10
-5
0
5
10
Outdoor air temperature °C
Operating range - heating
Maximum water temperature at start-up (LWT) 3 °C max.
55
50
45
40
35
30
25
20
15
-15
-10
-5
0
Outdoor air temperature °C
Important note:
Use of the buffes tank is not obligatory.
It may be necessary to use it to reach the minimum volumes shown
in table V.
Refer to the following example for the buffes tank:
Min
Max
V
207
253
V
360
440
15
20
25
30
35
40
45
50
5
10
15
20
25

Publicidad

Tabla de contenido
loading

Tabla de contenido