7
|
Instalación de las tuberías
Guía de referencia del instalador
42
Clase de capacidad total de la unidad interior que puede conectarse a esta
unidad:
Unidad exterior
2MXM68
3MXM40
3MXM52
3MXM68, 4MXM68
4MXM80
5MXM90
Puerto
2MXM68
A (Ø9,5 mm)
B (Ø12,7 mm)
3MXM40
A (Ø9,5 mm)
B + C (Ø12,7 mm)
3MXM52
A (Ø9,5 mm)
B + C (Ø12,7 mm)
3MXM68
A (Ø9,5 mm)
B + C (Ø12,7 mm)
4MXM68
A + B (Ø9,5 mm)
C + D (Ø12,7 mm)
4MXM80
A (Ø9,5 mm)
B (Ø12,7 mm)
C + D (Ø15,9 mm)
5MXM90
A + B (Ø9,5 mm)
Clase de capacidad total de la unidad
interior
≤10,2 kW
≤7,0 kW
≤9,0 kW
≤11,0 kW
≤14,5 kW
≤15,6 kW
Clase
(a)
15, 20, 25, 35, (42)
(a)
15, 20, 25, 35, (42)
42, 50, 60
15, 20, 25, 35
15, 20, 25, 35
(a)
15, 20, 25, 35, (42)
15, 20, 25, 35
42, 50
(a)
15, 20, 25, 35, (42)
15, 20, 25, 35, 42
50, 60
(a)
15, 20, 25, 35, (42)
(a)
15, 20, 25, 35, (42)
42, 50, 60
(a)
15, 20, 25, 35, (42)
(a)
15, 20, 25, 35, (42)
42, 50, 60
(a)
15, 20, 25, 35, (42)
42, 50, 60
71
(a)
15, 20, 25, 35, (42)
Reductor
—
2+4
—
—
2+4
—
2+4
—
—
2+4
—
—
2+4
—
—
2+4
—
5+6
1+3
—
—
2MXM-A, 3MXM-A, 4MXM-A, 5MXM-A
Serie Split R32
4P600463-5E – 2021.12