Installation; Boiler Fixing - Riello Burners 40 FSP10 Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

TEST BOILER
The working field has been defined according to EN 676 standard.
COMMERCIAL BOILERS
The burner-boiler matching is assured if the boiler conforms to EN 303 and the combustion chamber dimen-
sions are similar to those shown in the diagram EN 676. For applications where the boiler does not conform to
EN 303, or where the combustion chamber is much smaller than the dimensions given in EN 676, please con-
sult the manufacturers.
CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT
To obtain the maximum output, a gas head pressure of 8.4 mbar is measured (M2, see chapter 3.3, page 4) with
the combustion chamber at 0 mbar using gas G31 with a net heat value of 24,44 kWh/Sm
10
8
6
4
2
0
50
D7341
50.000
3.

INSTALLATION

THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.

3.1 BOILER FIXING

IMPORTANT
Boiler door must have a max. thickness of 90 mm,
refractory lining included.
If thickness is greater (max. 150 mm), a combustion
head extension must be fitted, which is supplied
separately.
HINGE
ASSEMBLY
3290
80
60
70
70.000
60.000
S7392
90
100
80.000
90.000
Thermal power
Separate the combustion-head assembly
from the burner body by removing nut (1) and
removing group (A).
Fix the head assembly group (B) to the boiler
(2) insert the supplied insulating gasket (3).
A
3
GB
3
(21.000 kcal/Sm
120 kW
110
kcal/h
100.000
1
3
D5108
B
3
).
2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

564 t303756439

Tabla de contenido