Starting from display is in active mode, the controller settings can be edit in the following way:
1. Press both arrow buttons together until the display shows 0000.
2. Then press short "up", to show P001 = Parameter 1.
3. Use "up" or "down" to step through the parameter list.
4. Press shortly the On/Off button to go in edit mode. Setting value is shown and flashes.
5. Edit the value by arrow buttons "up" or "down".
6. Confirm your edit with press the On/Off button. Display jumps back to the parameter
number.
If the display is left in the Parameter menu for more than 10 seconds without any activity
(buttons pressed), the controller will automatically exit the parameter menu. The parameter
menu can also be left, with the selection of "EXIT" and confirm with On/Off.
The most important parameters are:
No.
Description
P001 Basic setpoint (SPbasic)
Hysteresis used for setpoint calculation at Occupied state
P002
(heating and cooling)
Hysteresis used for setpoint calculation at Standby state
P003
(heating and cooling)
SETTINGS
Basic Min
Max
20°C
5
50
1K
1
10
5K
1
30