14 - LIST OF PARAMETERS
A
CONSTANT PRESSURE
B
DIFFERENTIAL PRESSURE
C
FIXED SPEED
Par.
Description
Units
1.1
PRESSURE SETPOINT
Bar
Hz
1.2
SPEED SETPOINT
TEMPERATURE SETPOINT
1.3
MOTOR CURRENT
Amp
1.4
1.5
ROTATION DIRECTION
1.6
STOP FREQUENCY
Hz
START-UP DIFFERENTIAL
1.7
Bar
STOP TEMPERATURE
1.8
OFFSET
Par.
Description
Units
2.01
MODULE TEMPERATURE
2.02
mA
ANALOGUE SIGNAL 1
mA
2.03
ANALOGUE SIGNAL 2
2.04
0-10V INPUT
MOTOR THERMISTOR
kohm
2.05
2.06
VOLTAGE HOURS
Hours
HOURS WORKED
2.07
Hours
2.08
START-UP NUMBER
2.09
DIGITAL INPUT 1
2.10
DIGITAL INPUT 2
2.11
DIGITAL INPUT 3
DIGITAL INPUT 4
2.12
2.13
RELAY 1 OUTPUT
RELAY 2 OUTPUT
2.14
2.15
SOFTWARE VERSION
CONS. POWER OF PUMP
2.16
CONS. POWER OF GROUP
2.17
MODE
D
CONSTANT TEMPERATURE
E
DIFFERENTIAL TEMPERATURE
Programming
Default
Min.
Wizard
0,5
Wizard
10
ºC
Wizard
11 (MT 2200)
Wizard
0,1
11 (TT 4000)
30 (TT 11000)
0
Wizard
0,1
0,5
0,3
ºC
Wizard
0,1
ºC
This indicates the temperature the electronic module of the inverter.
This indicates the value in mA of the pressure transducer 1.
This data will be 4 mA for 0 Bar and 20 mA for the upper limit of the transducer connected.
This indicates the value in mA of the pressure transducer 2.
This data will be 4 mA for 0 Bar and 20 mA for the upper limit of the transducer connected.
V
This indicates the value of the 0-10V signal if it is enabled in one of the inputs.
This indicates the value of the NTC/PTC signal if it is enabled on settings.
This indicates the total number of hours the inverter has been connected to an electricity grid.
This indicates the total number of hours worked (providing an output voltage) of the inverter.
This indicates the total number of start-ups from zero that the unit has made.
This indicates whether digital input 1 is ON or OFF.
This indicates whether digital input 2 is ON or OFF.
This indicates whether digital input 3 is ON or OFF.
This indicates whether digital input 4 is ON or OFF.
This indicates whether the relay 1 output is ON or OFF.
This indicates whether the relay 2 output is ON or OFF.
Version of the unit software.
W
Instantaneous power consumed in output terminals toward pump.
W
Power consumed instantaneously by all of the pumps.
Wizard: This parameter is the one entered or calculated in the start-up wizard.
FS: Full-scale value of the transducer (entered in the start-up wizard).
1. PARAMETERS
Notes
Max.
FS
Pressure you wish to maintain in the system.
65
Speed you wish to maintain in the system.
Temperature you wish to maintain in the system.
Current of the motor in amperes. Taking into account
whether your motor is wired as three phase 230V or three
phase 400V. Insert nominal value.
You can change the rotation direction of the motor by
1
modifying this parameter from 0 to 1 or vice versa.
The system will stop when the Inverter has been working
99,9
for a certain time (see parameter 5.12) under this
frequency.
This is the differential that enables you to reduce the
pressure to start the pump using the value entered in
3
parameter 1.1.
This is the offset temperature for the temperature
100
setpoint.
2. DISPLAY
Notes
29
EN
Application
A
B
C
D
E
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Application
A
B
C
D
E
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X